Doc# E149701 5 - 10
5: Communication Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Valid Communication Settings are as follows:
COM1 (IrDA)
Response Delay (0-750 msec)
COM2 (RS485)
Address (1-247; for DNP ONLY 1 - 65520)
Protocol (Modbus RTU, Modbus ASCII or DNP)
Baud Rate (1200 to 57600) Your meter must have Runtime Firmware Version
26 or higher to set Baud rates of 1200, 2400, and 4800.
Response Delay (0-750 msec)
Parity (Odd, Even, or None) Your meter must have Runtime Firmware
version 26 or higher to be able to set Parity.
DNP Options for Voltage, Current, and Power - these fields allow you to choose Pri-
mary or Secondary Units for DNP, and to set custom scaling if you choose Primary.
Click the Optimal Scaling button to have the software choose a divisor for voltage,
current, and power, that will not result in an over/under-range.
NOTE: You must set the DNP polling software to multiply by the divisor amount
before showing the final value.
See Chapter 5 in the Communicator EXT
TM
User Manual for more information.
8. When changes are complete, click the Update Device button to send a new profile
to the meter.
9. Click Exit to leave the Device Profile or click other menu items to change other
aspects of the Device Profile (see the following section for instructions).