Electro Industries Shark 200T Spezifikationen Seite 196

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 298
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 195
Doc# E149701 B - 36
B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
NOTES:
• An I/O Change log record will be taken for each Relay and Digital Input that has
been configured in the Programmable Settings to record when its state changes.
• When any one configured Relay or Digital Input changes, the values of all Relays
and Digital Inputs are recorded, even if they are not so configured.
B.5.6: Examples
Log Retrieval Section:
send: 01 03 75 40 00 08 - Meter designation
recv: 01 03 10 4D 65 74 72 65 44 65 73 69 6E 67 5F 20 20 20 20 00 00
send: :01 03 C7 57 00 10 - Historical Log 1 status block
recv: :01 03 20 00 00 05 1E 00 00 05 1E 00 2C 00 00 06 08 17 51 08
00 06 08 18 4E 39 00 00 00 00 00 00 00 00 00 00 00
send: :01 03 79 17 00 40 - Historical Log 1 PS settings
recv: :01 03 80 13 01 00 01 23 75 23 76 23 77 1F 3F 1F 40 1F 41 1F
42 1F 43 1F 44 06 0B 06 0C 06 0D 06 0E 17 75 17 76 17 77 18
67 18 68 18 69 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00
send: :01 03 79 57 00 40 - ""
recv: :01 03 80 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00 00 00 00 00 00 62 62 62 34 34 34 44
44 62 62 62 62 62 62 00 00 00 00 00 00
send: :01 03 75 35 00 01 - Energy PS settings
recv: :01 03 02 83 31 00 00
send: :01 03 11 93 00 01 - Connected Port ID
recv: :01 03 02 00 02 00 00
send: :01 03 C7 57 00 10 - Historical Log 1 status block
recv: :01 03 20 00 00 05 1E 00 00 05 1E 00 2C 00 00 06 08 17 51 08
00 06 08 18 4E 39 00 00 00 00 00 00 00 00 00 00 00
Seitenansicht 195
1 2 ... 191 192 193 194 195 196 197 198 199 200 201 ... 297 298

Kommentare zu diesen Handbüchern

Keine Kommentare