Doc# E149701 6 - 15
6: Using the Shark® 200 Meter
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6.2.6: Using Operating Mode
Operating mode is the Shark® 200 meter’s default mode, that is, the standard front
panel display. After starting up, the meter automatically scrolls through the parameter
screens, if scrolling is enabled. Each parameter is shown for 7 seconds, with a 1 sec-
ond pause between parameters. Scrolling is suspended for 3 minutes after any button
is pressed.
1. Press the Down button to scroll all the parameters in Operating mode. The
currently “Active,” i.e., displayed, parameter has the Indicator light next to it, on
the right face of the meter.
2. Press the Right button to view additional readings for that parameter. The table
below shows possible readings for Operating Mode. Sheet 2 in Appendix A shows
the Operating mode Navigation map.
NOTE: Readings or groups of readings are skipped if not applicable to the meter type
or hookup, or if they are disabled in the programmable settings.
OPERATING MODE PARAMETER READINGS
POSSIBLE READINGS
VOLTS L-N VOLTS_LN VOLTS_LN_
MAX
VOLTS_LN_
MIN
VOLTS_LN_
THD
VOLTS L-L VOLTS_LL VOLTS_LL_MAX VOLTS_LL_MIN
AMPS AMPS AMPS_NEUTRAL AMPS_MAX AMPS_MIN AMPS_THD
W/VAR/PF W_VAR_PF W_VAR_PF_MA
X_POS
W_VAR_PF_MIN
_POS
W_VAR_PF_
MIN_NEG
VA/Hz VA_FREQ VA_FREQ_MAX VA_FREQ_MIN
Wh KWH_REC KWH_DEL KWH_NET KWH_TOT
VARh KVARH_POS KVARH_NEG KVARH_NET KVARH_TOT
VAh KVAH