Doc# E149701 C - 11
C: DNP Mapping
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
30 15 4 Positive Watts,
3-Ph,
Maximum Avg
Demand
SINT16 -32768 to
+32767
(4500 /
32768)
W
30 16 4 Positive VARs,
3-Ph,
Maximum Avg
Demand
SINT16 -32768 to
+32767
(4500 /
32768)
VAR
30 17 4 Negative
Watts, 3-Ph,
Maximum Avg
Demand
SINT16 -32768 to
+32767
(4500 /
32768)
W
30 18 4 Negative
VARs, 3-Ph,
Maximum Avg
Demand
SINT16 -32768 to
+32767
(4500 /
32768)
VAR
30 19 4 VAs, 3-Ph,
Maximum Avg
Demand
SINT16 -32768 to
+32767
(4500 /
32768)
VA
30 20 4 Angle, Phase A
Current
SINT16 -1800 to
+1800
0.1 degree
30 21 4 Angle, Phase B
Current
SINT16 -1800 to
+1800
0.1 degree
30 22 4 Angle, Phase C
Current
SINT16 -1800 to
+1800
0.1 degree
30 23 4 Angle, Volts
A-B
SINT16 -1800 to
+1800
0.1 degree
30 24 4 Angle, Volts
B-C
SINT16 -1800 to
+1800
0.1 degree
30 25 4 Angle, Volts
C-A
SINT16 -1800 to
+1800
0.1 degree
30 26 4 CT numerator SINT16 1 to 9999 N/A none CT ratio =
(numerator
* multiplier)
/ denomina-
tor
30 27 4 CT multiplier SINT16 1, 10, or 100 N/A none
30 28 4 CT
denominator
SINT16 1 or 5 N/A none
30 29 4 PT numerator SINT16 1 to 9999 N/A none PT ratio =
(numerator
* multiplier)
/ denomina-
tor
30 30 4 PT multiplier SINT16 1, 10, or 100 N/A none
30 31 4 PT
denominator
SINT16 1 to 9999 N/A none
Object Point Var Description Format Range Multiplier Units Comments