B: Modbus Map and Retrieving Logs
Doc# E149701 MM-15
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
24E7 - 24E9 9448 - 9450 Frequency, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24EA - 24EC 9451 - 9453 Neutral Current, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2100 1 sec 3
24ED - 24EF 9454 - 9456 Positive Watts, Phase A, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24F0 - 24F2 9457 - 9459 Positive Watts, Phase B, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24F3 - 24F5 9460 - 9462 Positive Watts, Phase C, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24F6 - 24F8 9463 - 9465 Positive VARs, Phase A, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24F9 - 24FB 9466 - 9468 Positive VARs, Phase B, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24FC - 24FE 9469 - 9471 Positive VARs, Phase C, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
24FF - 2501 9472 - 9474 Negative Watts, Phase A, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2502 - 2504 9475 - 9477 Negative Watts, Phase B, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2505 - 2507 9478 - 9480 Negative Watts, Phase C, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2508 - 250A 9481 - 9483 Negative VARs, Phase A, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
250B - 250D 9484 - 9486 Negative VARs, Phase B, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
250E - 2510 9487 - 9489 Negative VARs, Phase C, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2511 - 2513 9490 - 9492 VAs, Phase A, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2514 - 2516 9493 - 9495 VAs, Phase B, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2517 - 2519 9496 - 9498 VAs, Phase C, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
251A - 251C 9499 - 9501 Positive PF, Phase A, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
251D - 251F 9502 - 9504 Positive PF, Phase B, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2520 - 2522 9505 - 9507 Positive PF, Phase C, Max Avg Dmd Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2523 - 2525 9508 - 9510 Negative PF, Phase A, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2526 - 2528 9511 - 9513 Negative PF, Phase B, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2529 - 252B 9514 - 9516 Negative PF, Phase C, Max Avg Dmd
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
252C - 252E 9517 - 9519 Volts A-N, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
252F - 2531 9520 - 9522 Volts B-N, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2532 - 2534 9523 - 9525 Volts C-N, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2535 - 2537 9526 - 9528 Amps A, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2538 - 253A 9529 - 9531 Amps B, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
253B - 253D 9532 - 9534 Amps C, %THD, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
253E - 2540 9535 - 9537 Symmetrical Comp Magnitude, 0 Seq, Max
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2541 - 2543 9538 - 9540 Symmetrical Comp Magnitude, + Seq, Max
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2544 - 2546 9541 - 9543 Symmetrical Comp Magnitude, - Seq, Max
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2547 - 2549 9544 - 9546 Symmetrical Comp Phase, 0 Seq, Max
Timestamp
TSTAMP
1Jan2000 - 31Dec2099 1 sec 3