B: Modbus Map and Retrieving Logs
Doc# E149701 MM-6
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
07F1 - 07F2 2034 - 2035 Negative Watts, Phase A, Average FLOAT -9999 M to +9999 M watts 2
07F3 - 07F4 2036 - 2037 Negative Watts, Phase B, Average FLOAT -9999 M to +9999 M watts 2
07F5 - 07F6 2038 - 2039 Negative Watts, Phase C, Average FLOAT -9999 M to +9999 M watts 2
07F7 - 07F8 2040 - 2041 Negative VARs, Phase A, Average FLOAT -9999 M to +9999 M VARs 2
07F9 - 07FA 2042 - 2043 Negative VARs, Phase B, Average FLOAT -9999 M to +9999 M VARs 2
07FB - 07FC 2044 - 2045 Negative VARs, Phase C, Average FLOAT -9999 M to +9999 M VARs 2
07FD - 07FE 2046 - 2047 VAs, Phase A, Average FLOAT -9999 M to +9999 M VAs 2
07FF - 0800 2048 - 2049 VAs, Phase B, Average FLOAT -9999 M to +9999 M VAs 2
0801 - 0802 2050 - 2051 VAs, Phase C, Average FLOAT -9999 M to +9999 M VAs 2
0803 - 0804 2052 - 2053 Positive PF, Phase A, Average FLOAT -1.00 to +1.00 none 2
0805 - 0806 2054 - 2055 Positive PF, Phase B, Average FLOAT -1.00 to +1.00 none 2
0807 - 0808 2056 - 2057 Positive PF, Phase C, Average FLOAT -1.00 to +1.00 none 2
0809 - 080A 2058 - 2059 Negative PF, Phase A, Average FLOAT -1.00 to +1.00 none 2
080B - 080C 2060 - 2061 Negative PF, Phase B, Average FLOAT -1.00 to +1.00 none 2
080D - 080E 2062 - 2063 Negative PF, Phase C, Average FLOAT -1.00 to +1.00 none 2
Block Size: 64
read-only
0BB7 - 0BB8 3000 - 3001 Watts, 3-Ph total FLOAT -9999 M to +9999 M watts 2
0BB9 - 0BBA 3002 - 3003 VARs, 3-Ph total FLOAT -9999 M to +9999 M VARs 2
0BBB - 0BBC 3004 - 3005 VAs, 3-Ph total FLOAT -9999 M to +9999 M VAs 2
0BBD - 0BBE 3006 - 3007 Power Factor, 3-Ph total FLOAT -1.00 to +1.00 none 2
0BBF - 0BC0 3008 - 3009 Watts, Phase A FLOAT -9999 M to +9999 M watts 2
0BC1 - 0BC2 3010 - 3011 Watts, Phase B FLOAT -9999 M to +9999 M watts 2
0BC3 - 0BC4 3012 - 3013 Watts, Phase C FLOAT -9999 M to +9999 M watts 2
0BC5 - 0BC6 3014 - 3015 VARs, Phase A FLOAT -9999 M to +9999 M VARs 2
OBC7 - 0BC8 3016 - 3017 VARs, Phase B FLOAT -9999 M to +9999 M VARs 2
0BC9 - 0BCA 3018 - 3019 VARs, Phase C FLOAT -9999 M to +9999 M VARs 2
0BCB - 0BCC 3020 - 3021 VAs, Phase A FLOAT -9999 M to +9999 M VAs 2
0BCD - 0BCE 3022 - 3023 VAs, Phase B FLOAT -9999 M to +9999 M VAs 2
0BCF - 0BD0 3024 - 3025 VAs, Phase C FLOAT -9999 M to +9999 M VAs 2
0BD1 - 0BD2 3026 - 3027 Power Factor, Phase A FLOAT -1.00 to +1.00 none 2
0BD3 - 0BD4 3028 - 3029 Power Factor, Phase B FLOAT -1.00 to +1.00 none 2
0BD5 - 0BD6 3030 - 3031 Power Factor, Phase C FLOAT -1.00 to +1.00 none 2
0BD7 - 0BD8 3032 - 3033 W-hours, Received SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BD9 - 0BDA 3034 - 3035 W-hours, Delivered SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BDB - 0BDC 3036 - 3037 W-hours, Net SINT32 -99999999 to 99999999 Wh per energy format 2
0BDD - 0BDE 3038 - 3039 W-hours, Total SINT32 0 to 99999999 Wh per energy format 2
0BDF - 0BE0 3040 - 3041 VAR-hours, Positive SINT32 0 to 99999999 VARh per energy format 2
0BE1 - 0BE2 3042 - 3043 VAR-hours, Negative SINT32 0 to -99999999 VARh per energy format 2
0BE3 - 0BE4 3044 - 3045 VAR-hours, Net SINT32 -99999999 to 99999999 VARh per energy format 2
0BE5 - 0BE6 3046 - 3047 VAR-hours, Total SINT32 0 to 99999999 VARh per energy format 2
0BE7 - 0BE8 3048 - 3049 VA-hours, Total SINT32 0 to 99999999 VAh per energy format 2
0BE9 - 0BEA 3050 - 3051 W-hours, Received, Phase A SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
0BEB - 0BEC 3052 - 3053 W-hours, Received, Phase B SINT32 0 to 99999999 or
0 to -99999999
Wh per energy format 2
Uncompensated Readings Block
Per phase power and PF have values
only for WYE hookup and will be
zero for all other hookups.
* Wh received & delivered always have opposite signs
* Wh received is positive for "view as load", delivered is
positive for "view as generator"
* 5 to 8 digits
* decimal point implied, per energy format
* resolution of digit before decimal point = units, kilo, or
mega, per energy format