B: Modbus Map and Retrieving Logs
Doc# E149701 MM-29
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
7E1F - 7E1F 32288 - 32288 Input#1 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
7E20 - 7E20 32289 - 32289 Input#2 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
7E21 - 7E21 32290 - 32290 Input#3 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
7E22 - 7E22 32291 - 32291 Input#4 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
7E23 - 7F3E 32292 - 32575 Reserved Reserved 284
Block Size: 512
Second Overlay write only in PS update mode
7D3F - 7D3F 32064 - 32064 Update rate UINT16 0 to 65535 milliseconds Fixed -- see specifications. 1
7D40 - 7D40 32065 - 32065 Channel direction - 1mA Card only! UINT16 bit-mapped
-------- ----4321
Full range output for 0-1mA card only: A bit set(1) means
full range (-1mA to +1mA); a bit cleared(0) means source
only (0mA to +1mA).
1
7D41 - 7D41 32066 - 32066 Format parameter for output #1 UINT16 bit-mapped
-------- ---f suwb
Format of the polled register:f=float 32; s=signed 32 bit
int; u=unsigned 32 bit int; w=signed 16 bit int;
b=unsigned 16 bit int.
1
7D42 - 7D42 32067 - 32067 Source register for Output#1 UINT16 0 to 65535 This register should be programmed with the address of
the register whose value is to be used for current output.
In different words, the current level output of analog
board will follow the value of the register addressed here.
1
7D43 - 7D44 32068 - 32069 High value of source register for output#1 Value read from the source register at which High
nominal current will be output. Example: for the 4-20mA
card, if this register is programmed with 750, then the
current output will be 20mA when the value read from the
source register is 750.
2
7D45 - 7D46 32070 - 32071 Low value of source register for output#1 Value read from the source register at which Low
nominal current will be output. Example: for the 4-20mA
card, if this register is programmed with 0, then the
current output will be 4mA when the value read from the
source register is 0.
2
7D47 - 7D4C 32072 - 32077 Analog output#2 format, register, max & min 6
7D4D - 7D52 32078 - 32083 Analog output#3 format, register, max & min 6
7D53 - 7D58 32084 - 32089 Analog output#4 format, register, max & min 6
7D59 - 7F3E 32090 - 32575 Reserved Reserved 486
Block Size: 512
Second Overlay write only in PS update mode
7D3F - 7D3F 32064 - 32064 General Options bit-mapped
-----DGT W--- -1--
W=Web server:0=Enabled, 1=Disabled
T=Silentmode:0=Disabled, 1=Enabled
(When enabled TCP/Reset is not sent when
Connection is attempted to an unbound port)
G=Modbus Tcp/Ip Gateway:0=Enabled,1=Disabled
D=DNP-Tcp/Ip-Wrapper: 0=Disabled, 1=Enabled.
1
7D40 - 7D40 32065 - 32065 DHCP enable bit-mapped
-------- -------d
DHCP: d=1 enabled, d=0 disabled (user must provide IP
configuration).
1
KT power factor for the accumulator input
"V" is raw power value in Wh/pulse from 0 to 9999.
"dd"=decimal point position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
Settings Registers for Analog Out 0-1mA / Analog Out 4-20mA Cards
Depends on the format parameter
Depends on the format parameter
Same as analog output#1
Same as analog output#1
Same as analog output#1
Settings Registers for Network Cards