Electro Industries Shark 200T Spezifikationen Seite 188

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 298
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 187
Doc# E149701 B - 28
B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Data:
Log Number: 0 (ignore)
Enable: 0 (Disengage log)
Scope: 0 (ignore)
----------------------------------------------------
Receive: 0106C34F0000 (echo)
NOTES:
• This disengages the log, allowing it to be retrieved by other COM ports.
• The log will automatically disengage if no log retrieval action is taken for 5 minutes.
B.5.5: Log Record Interpretation
The records of each log are composed of a 6 byte timestamp, and N data. The content
of the data portion depends on the log.
System Event Record:
Size: 14 bytes (20 bytes image).
Data: The System Event data is 8 bytes; each byte is an enumerated value.
• Group: Group of the event.
• Event: Event within a group.
• Modifier: Additional information about the event, such as number of sectors or log
number.
• Channel: The port of the Shark® 200 meter that caused the event.
0 Firmware
1 COM 1 (IrDA)
Byte 012345678910111213
Value timestamp Group Event Mod Chan Param1 Param2 Param3 Param4
Seitenansicht 187
1 2 ... 183 184 185 186 187 188 189 190 191 192 193 ... 297 298

Kommentare zu diesen Handbüchern

Keine Kommentare