Voltage Inputs
• 20-576 Volts Line To Neutral,
0-721 Volts Line to Line
• Universal Voltage Input
• Input Withstand Capability – Meets
IEEE C37.90.1 (Surge Withstand
Capability)
• Programmable Voltage Range to
Any PT ratio
• Supports: 3 Element WYE, 2.5
Element WYE, 2 Element Delta, 4
Wire Delta Systems
• Burden: Input Impedance 1 Mega
Ohms. Burden 0.014W at 120 Volts
• Input wire gauge max (AWG
12 / 2.5mm
2
)
Current Inputs
• Class 10: (0.005 to 11) A, 5 Amp
Nominal
• Class 2: (0.001 to 2) A, 1A Nominal
Secondary
• Fault Current Withstand (at 23°C):
100 Amps for 10 Seconds, 300
Amps for 3 Seconds, 500 Amps for
1 Second
• Continuous current withstand:
20 Amps for Screw Terminated or
Pass Through Connections
• Programmable Current to Any
CT Ratio
• Burden 0.005VA per phase Max at
11Amps
• Pickup Current: 0.1% of Nominal
Class 10: 5mA
Class 2: 1mA
• Pass through wire diameter:
0.177” / 4.5mm
Isolation
All Inputs and Outputs are
galvanically isolated to 2500 Volts
Environmental Rating
Storage: (-20 to +70)° C
Operating: (-20 to +70)° C
Humidity: to 95% RH Non-Condensing
Faceplate Rating: NEMA12
(Water Resistant)
Mounting Gasket Included
Sensing Method
• True RMS
• Sampling at over 400 samples /
cycle on all channels of measured
readings simultaneously
• Harmonics resolution to 40th order
• Waveform up to 512 samples/cycle
Update Rate
• Watts, VAR and VA - every 6 cycles
• All other parameters - every 60
cycles
Power Supply
Option D2:
• (90 to 265) Volts AC and (100 to 370)
Volts DC. Universal AC/DC Supply
Option D:
• (18-60) Volts DC (24-48 VDC Systems)
Burden: 10VA Max
Standard Communication Format
• 2 Com Ports (Back and Faceplate)
• RS485 Port (Through Backplate)
• IrDA (Through Faceplate)
• Com Port Baud Rate: (1200 - 57600)
• Com Port Address: 1-247
• 8 Bit, No parity
• Modbus RTU, ASCII or DNP 3.0
Protocols
KYZ Pulse
• Type Form C Contact
• On Resistance: 35 Ohms Max
• Peak Voltage: 350 VDC
• Continuous Load Current: 120mA
• Peak Load Current: 350mA (10ms)
• Off State Leakage Current@
350VDC: 1uA
Dimensions and Shipping
• Weight: 2 lbs
• Basic Unit: H4.85" x W4.85" x L4.25"
• Shark® 200 meter mounts in 92mm
DIN & ANSI C39.1 4" round cut-outs
• Shark® 200T Transducer DIN rail
mounted
• 2-inch DIN Rail Included
• Shipping Container Dimensions:
6” cube
Meter Accuracy
• See page 2
• Note: For 2.5 element programmed
units, degrade accuracy by an
additional 0.5% of reading.
• Note: For 1A (Class 2) Nominal,
degrade accuracy to 0.5% of reading
for watts and energy; all other values 2
times rated accuracy.
Compliance
• IEC 62053-22 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge
Withstand
• ANSI C62.41 (Burst)
• EN61000-6-2 – Immunity for
Industrial Environments: 2005
• EN61000-6-4 – Emission Standards
for Industrial Environments: 2007
• EN61326-1 - EMC Requirements:
2006
8
Electro Industries/GaugeTech
1800 Shames Drive • Westbury, NY 11590
Tel: 516-334 -0870 • Web Site: www.electroind.com • Fax: 516-338-4741
Model Frequency Current Input V-Switch Pack
Shark200
(Meter/Transducer)
Shark200T
(Transducer Only)
All fields must be filled in to create a valid part number.
Additional Accessories
Option
Numbers:
Example: Shark200
60
50
50 Hz
System
60
60 Hz
System
10
10
10 Amp
Secondary
2
2 Amp
Secondary
-
-
-
-
V2
V1
Multifunction
Meter Only
V2
Standard Data-
Logging Memory
V3
Power Quality Harmonics
V4
Limits & Control
V5
64 Samples/cycle
Waveform Recording
V6
512 Samples/cycle
Waveform Recording
-
-
-
-
-
-
Power Supply
D2
D2
90-265V
AC/DC
D
18-60V
DC
-
-
Communication Converters
9PINC – RS232 Cable
CAB6490 - USB to IrDA Adapter
Unicom 2500 - RS485 to RS232 Converter
Unicom 2500-F – RS485 to RS232 to Fiber Optic
Converter
Modem Manager, Model #, MM1 – RS485 to RS232
Converter for Modem Communication
IrDA232 - IrDA to RS232 Adapter for Remote Read
Compliance Documents
Certificate of Calibration, Part #: CCal – This provides
Certificate of Calibration with NIST traceable Test Data.
Current Transformer Kits
CT200K – 200/5 Ratio 1.00” Window 3 CTs
CT400K – 400/5 Ratio, 1.25” Window, 3 CTs
CT800K – 800/5 Ratio, 2.06” Window, 3 CTs
CT2000K – 2000/5 Ratio, 3.00” Window, 3 CTs
CT Specifications:
Frequency: 50 to 400Hz; Insulation: 600 Volts, 10kV BIL
Flexible Leads: UL 1015 105°C, CSA Approved, 24”
Long, #16AWG
Software Option Numbers
COMEXT3 – CommunicatorEXT 3.0 for Windows®
* Consult factory application engineer for additional
transformer ratios, types or window sizes.
I/O Slot 1* I/O Slot 2*
INP100S
X
None
RO1S
2 Relays /
2 Status
PO1S
4 Pulses /
4 Status
1mAOS
4 channel
Analog Output
0-1
(bidirectional)
20mAOS
4 Channel
Analog Output
4-20mA
FOSTS
Fiber Optic
Output ST
Terminated
FOVPS
Fiber Optic
Output VPIN
Terminated
INP100S
100BaseT
Ethernet
X
X
None
RO1S
2 Relays /
2 Status
PO1S
4 Pulses /
4 Status
1mAOS
4 channel
Analog Output
0-1
(bidirectional)
20mAOS
4 Channel
Analog Output
4-20mA
FOSTS
Fiber Optic
Output ST
Terminated
FOVPS
Fiber Optic
Output VPIN
Terminated
INP100S
100BaseT
Ethernet
* I/O cards can be ordered separately
using the above part numbers.