B: Modbus Map and Retrieving Logs
Doc# E149701 MM-27
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
write only in PS update mode
7CFF - 7CFF 32000 - 32000 Class ID of the Option Card 1 Settings UINT16 bit-mapped -------- cccctttt Which class (cccc) and type(tttt) of card the Option
Settings for Card 1 apply to. See note 22.
1
7D00 - 7D3E 32001 - 32063 Settings for Option Card 1, First Overlay -- see
below
63
7D3F - 7F3E 32064 - 32575 Settings for Option Card 1, Second Overlay --
see below
512
Block Size: 576
First Overlay write only in PS update mode
7D00 - 7D00 32001 - 32001 Slave address UINT16 1~247 (for Modbus)
1~65534 (for DNP)
none Slave address of the unit. The communication capable
card is always a master.
Set to 0 when an analog board is installed.
1
7D01 - 7D01 32002 - 32002 Speed and format UINT16 bit-mapped
-abcde--fghijklm
Bps: a=57600; b=38400; c=19200; d=14400; e=9600
Stop bits 'f': cleared 1 stop bit, set 2 stop bits
Parity: g=even; h=odd; i=none
Data bits: j=8; k=7; l=6; m=5
Set to 0 when an analog board is installed.
1
7D02 - 7D02 32003 - 32003 Reserved Reserved 1
7D03 - 7D03 32004 - 32004 Protocol UINT16 bit-mapped
-------- -----ppp-
ppp= 100 =DNP3; 010=Ascii Modbus; 001=Rtu Modbus
Set to 0 when an analog board is installed.
1
7D04 - 7D04 32005 - 32005 Reply delay UINT16 0 to 65535 milliseconds Delay to reply to a Modbus transaction after receiving it.
Set to 0 when an analog board is installed
1
7D05 - 7D3E 32006 - 32063 Reserved Reserved 58
Block Size: 63
First Overlay write only in PS update mode
7D00 - 7D00 32001 - 32001 Input#1 - 2 bindings & logging enables UINT16 bit-mapped
-------- 2222 1111
One nibble for each input.
Assuming "abcc" as the bits in each nibble:
"a": select this input for EOI (End Of Interval)pulse
sensing.
"b": log this input when pulse is detected
"cc": Input event trigger mode - Contact sensing method;
00 = none; 01 = op
en to close; 10 = close to open; 11 =
any change.
Every input has an associated internal accumulator (See
input Accumulator Scaling), which is incremented every
time the input changes according with the trigger mode
crieteria “cc”
1
7D01
-
7D01 32002 - 32002 Relay #1 Delay to Operate UINT16 0.1 second units Delay to operate the relay since request. 1
7D02 - 7D02 32003 - 32003 Relay #1 Delay to Release UINT16 0.1 second units Delay to release the relay since request. 1
7D03 - 7D08 32004 - 32009 Reserved UINT16 Set to 0. 6
7D09 - 7D09 32010 - 32010 Relay #2 Delay to Operate UINT16 0.1 second units Delay to operate the relay since request. 1
7D0A - 7D0A 32011 - 32011 Relay #2 Delay to Release UINT16 0.1 second units Delay to release the relay since request. 1
7D0B - 7D20 32012 - 32033 Reserved UINT16 Set to 0. 22
Overlays for Option Card 1 Programmable Settings
Settings Registers for any communication capable card, including network and analog cards
Settings Registers for Digital I/O Relay Card
Programmable Settings for Option Card 1
Option Card 1 Setups Block
Register assignments depend on which type of card is in the slot. See overlays below.
Register assignments depend on which type of card is in the slot. See overlays below.
Seitenansicht 214