Specifications
Ordering Information
Model
Frequency
CurrentInput
V-SwitchPack
Shark200
(Meter/Transducer)
Shark200T
(TransducerOnly)
All fields must be filled in to create a valid part number.
Additional Accessories
Option
Numbers:
Example: Shark200
-60
-50
50 Hz
System
-60
60 Hz
System
-10
-10
10 Amp
Secondary
-2
2 Amp
Secondary
-
-
-
-
-V2
-V1
Multifunction
Meter Only
-V2
Standard Data-
Logging Memory
-V3
Power Quality Harmonics
-V4
Limits & Control
-V5
64 Samples/cycle
Waveform Recording
-V6
512 Samples/cycle
Waveform Recording
-
-
-
-
-
-
PowerSupply
-D2
-D2
90-265V
AC/DC
-D
18-60V
DC
-
-
CommunicationConverters
9PINC – RS232 Cable
CAB6490 - USB to IrDA Adapter
Unicom 2500 - RS485 to RS232 Converter
Unicom 2500-F – RS485 to RS232 to Fiber Optic
Converter
Modem Manager, Model #, MM1 – RS485 to RS232
Converter for Modem Communication
IrDA232 - IrDA to RS232 Adapter for Remote Read
ComplianceDocuments
Certificate of Calibration, Part #: CCal – This provides
Certificate of Calibration with NIST traceable Test Data.
CurrentTransformerKits
CT200K – 200/5 Ratio .94” Window 3 CTs
CT400K – 400/5 Ratio, 1.25” Window, 3 CTs
CT800K – 800/5 Ratio, 2.06” Window, 3 CTs
CT2000K – 2000/5 Ratio, 3.00” Window, 3 CTs
CTSpecifications:
Frequency: 50 to 400Hz; Insulation: 600 Volts, 10kV BIL
FlexibleLeads: UL 1015 105°C, CSA Approved, 24”
Long, #16AWG
Software Option Numbers
COMEXT3 – CommunicatorEXT 3.0 for Windows®
* Consult factory application engineer for additional
transformer ratios, types or window sizes.
Electro Industries/GaugeTech
1800ShamesDrive•Westbury,NY11590
Tel: 516-334-0870•Web Site:www.electroind.com•Fax: 516-338-4741
I/OSlot1* I/OSlot2*
-INP100S
-X
None
-RO1S
2 Relays /
2 Status
-PO1S
4 Pulses /
4 Status
-1mAOS
4 channel
Analog Output
0-1
(bidirectional)
-20mAOS
4 Channel
Analog Output
4-20mA
-FOSTS
Fiber Optic
Output ST
Terminated
-FOVPS
Fiber Optic
Output VPIN
Terminated
-INP100S
100BaseT
Ethernet
-X
-X
None
-RO1S
2 Relays /
2 Status
-PO1S
4 Pulses /
4 Status
-1mAOS
4 channel
Analog Output
0-1
(bidirectional)
-20mAOS
4 Channel
Analog Output
4-20mA
-FOSTS
Fiber Optic
Output ST
Terminated
-FOVPS
Fiber Optic
Output VPIN
Terminated
-INP100S
100BaseT
Ethernet
* I/O cards can be ordered separately
using the above part numbers.
Voltage Inputs
• 20-576 Volts Line To Neutral,
0-721 Volts Line to Line
• Universal Voltage Input
• Input Withstand Capability – Meets
IEEE C37.90.1 (Surge Withstand
Capability)
• Programmable Voltage Range to
Any PT ratio
• Supports: 3 Element WYE, 2.5
Element WYE, 2 Element Delta, 4
Wire Delta Systems
• Burden: Input Impedance 1 Mega
Ohms. Burden 0.014W at 120Volts
• Input wire gauge max (AWG
12 / 2.5mm
2
)
Current Inputs
• Class 10: (0.005 to 11) A, 5 Amp
Nominal
• Class 2: (0.001 to 2) A, 1A Nominal
Secondary
• Fault Current Withstand: 100
Amps for 10 Seconds, 300 Amps
for 3 Seconds, 500 Amps for 1 Second
• Continuous current withstand:
20 Amps for Screw Terminated or
Pass Through Connections
• Programmable Current to Any CT
Ratio
• Burden 0.005VA per phase Max at
11Amps
• Pickup Current: 0.1% of Nominal
Class 10: 5mA
Class 2: 1mA
• Pass through wire diameter:
0.177” / 4.5mm
Isolation
All Inputs and Outputs are
galvanically isolated to 2500 Volts
Environmental Rating
Storage: (-20 to +70)° C
Operating: (-20 to +70)° C
Humidity: to 95% RH Non-Condensing
Faceplate Rating:
NEMA12
(Water Resistant)
Mounting Gasket Included
Sensing Method
• True RMS
• Sampling at over 400 samples /
cycle on all channels of measured
readings simultaneously
• Harmonics resolution to 40th order
• Waveform up to 512 samples/cycle
Update Rate
• Watts, VAR and VA-100msec
• All other parameters-1second
Power Supply
Option D2:
• (90 to 265) Volts AC and (100 to 370)
Volts DC. Universal AC/DC Supply
Option: D:
• (18-60) Volts DC (24-48 VDC Systems)
Burden: 10VA Max
Standard Communication Format
• 2 Com Ports (Back and Face Plate)
• RS485 Port (Through Back Plate)
• IrDA (Through Faceplate)
• Com Port Baud Rate: (9,600 - 57,600)
• Com Port Address: 1-247
• 8 Bit, No parity
• Modbus RTU, ASCII or DNP 3.0
Protocols
KYZ Pulse
• Type Form C Contact
• On Resistance: 35 Ohms Max
• Peak Voltage: 350 VDC
• Continuous Load Current: 120mA
• Peak Load Current: 350mA (10ms)
• Off State Leakage Current @
350VDC: 1uA
Dimensions and Shipping
• Weight: 2 lbs
• Basic Unit: H4.85 x W4.85 x L4.65
• Shark® 200 meter mounts in 92mm
DIN & ANSI C39.1 Round Cut-outs
• Shark® 200T Transducer DIN rail
mounted
• 2-inch DIN Rail Included
• Shipping Container Dimensions:
6” cube
Meter Accuracy
• See page 3
•
Note: Accuracy specs doubled for 2.5
Element connections (less accurate).
Compliance:
• IEC 687 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge
Withstand
• ANSI C62.41 (Burst)
• IEC1000-4-2 – ESD
• IEC1000-4-3 – Radiated Immunity
• IEC 1000-4-4 – Fast Transient
• IEC 1000-4-5 – Surge Immunity
E 149702 121409 N Printed in China