1.INP100S:100BaseTEthernetCapability
The meter can provide 100BaseT Ethernet functionality.
Using this card, a user can connect to 12 simultaneous
Modbus TCP/IP connections.
2.
1mAOS:FourChannelBi-directional0-1mAOutputs
• Assignabletoanyparameter
• 0.1%offullscale
• 0to10KOhms,noaccuracylosses
• Range+/-1.20mA
3.20mAOS:FourChannel4-20mAOutputs
• Assignabletoanyparameter
• 0.1%offullscale
• 0–500Ohms,noaccuracylosses
• LoopPoweredusingupto24VoltsDC
4.RO1S:TwoRelayOutputs/TwoStatusInputs
• 250VAC/30VDC-5ARelays,FormC
• Triggeronusersetalarms
• Setdelaysandresetdelays
• StatusInputs–Wet/DryAutoDetect(Upto150VDC)
• MustbeusedwithV4orhigherV-Switch™optionfor
limit based alarms and control
5.PO1S:FourPulseOutputs/FourStatusInputs
• Programmabletoanyenergyparameterandpulsevalue
• FormA:Normallyopencontacts
• AlsousedforEndofIntervalpulse
• Canfunctionformanualrelaycontrolandlimitbased
control(V4-V6Options)
• 120mAcontinuousloadcurrent
• StatusInputs-Wet/DryAutoDetect(Upto150VDC)
6.FOVPSorFOSTS:FiberOpticCard
• EIG’sexclusiveFiberOpticDaisyChainswitchable
built-in logic mimics RS485 half duplex bus, allowing
you to daisy chain meters for lower installation costs.
Fullduplexisalsoassignable.
• STTerminatedOption(-FOST)
• VersatileLinkTerminatedOption(-FOVP)
• ModbusandDNP3.0protocolsavailable
4
RearMountedSerialPortwithKYZPulse
• RS485-ThisportallowsRS485communicationusingModbus
or DNP 3.0 Protocols. Baud rates are from 9600 to 57.6k.
• KYZPulse-InadditiontotheRS485,themeteralso
includes Pulse Outputs mapped to absolute energy.
FrontMountedIrDACommunication
Uniquely, the Shark® meter also has an optical IrDA port, allow-
ing the unit to be set up and programmed using a PDA or remote
laptop without need for a communication cable. Just point at the
meter with an IrDA-equipped PC or PDA and configure it. COPILOT
EXT is a Windows CE software package that allows you configure
the meter and poll readings.
The Shark® 200 meter provides two independent communication
ports with advanced features.
STANDARD COMMUNICATION CAPABILITY
FieldExpandableI/OSlots
FIELD EXPANDABLE I/O AND COMMUNICATION CAPABILITIES
Simple
Field
Upgrade
Meter Auto Detects I/O Card Type
TheShark®200 meteroffers unequaledI/O expandability. Using the two universal option slots, the unit can easily be
configured to accept new I/O cards even after installation. The unit auto-detects installed I/O option cards. Up to 2 cards
of any type can be used per meter.
Note: I/O cards can be ordered separately - see last page.